Application
Dynamic effective pressure transducer, electronic controller and actuator are fitted together in one casing
For clean air in ventilation and air-conditioning systems; the standard filtering enables use in the supply air without additional dust protection measures
Application examples: Offices and classrooms
In the event of a strong occurrence of dust, install appropriate extract air filters upstream, as a partial volume flow is routed through the transducer for volume flow rate measurement.
If the air is heavily contaminated with dust, fluff, sticky, moist components, use attachment group with static differential pressure transducer, e.g. XSMB0
Application examples: Extract air from changing rooms and shower areas, hospital bed rooms
Various control options based on setpoint value default setting
Volume flow rate control is based on setpoint values received from room temperature controller, MCE, air quality controller or other devices as an analogue signal or via communication interface
Override controls for activating qvmin, qvmax, shut-off, open position via Modbus/BACnet register or switch or relay possible
The actual volume flow rate is available as a network data point or as a linear voltage signal
Damper position, e.g. for fan optimisation, is available as a network data point
Control strategy
Operating modes
BACnet (B):
Analogue - variable operation (V):
Analogue - fixed value operation (F):
Alternative adjusting possible on site:
Interface
Communication interfaces
Analogue interface with adjustable signal voltage range
Note:
Parts and characteristics
Menu navigation for adjusting operating parameters
Menu navigation for customising the communication interface
Construction
Operating modes
BACnet (B):
Analogue - variable operation (V):
Analogue - fixed value operation (F):
Alternative adjusting possible on site:
1 Differential pressure transducer
2 Actuator
3 Volume flow controller
4 Setpoint value via BACnet, Modbus or analogue signal
5 Shaft with effective pressure channel
VAV terminal units control the volume flow in a closed loop, i.e. measurement – comparison – correction.
For volume flow rate measurement the effective pressure is measured first. This is done with a differential pressure sensor. The integral differential pressure transducer transforms the effective pressure into a voltage signal. The actual volume flow rate is available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal flow rate (qvnom).
The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS). Variable volume flow control results in a value between qvmin and qvmax. It is possible to override the room temperature control, e.g. by a complete shut-off of the duct.
The controller compares the differential pressure setpoint value to the actual value and controls the actuator accordingly if there is a difference.
Part number | Type of installation component | VAV terminal units |
AOOOOOO823O5 | TROVM-O24T-1Ol-DD15-BN | TVE, TVE-Q |
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Supply voltage (AC) | 24 V AC, ± 2O %, 5O/6O Hz |
Supply voltage (DC) | 24 V DC ± 2O % |
Power rating (AC) | TVE NW 1OO - 16O: maximum 4 VA TVE NW 2OO - 4OO: maximum 6 VA TVE-Q up to height 2OO: maximum 4 VA TVE-Q from height 3OO: maximum 6 VA |
Power rating (DC) | TVE NW 1OO - 16O: maximum 2.5 W TVE NW 2OO - 4OO: maximum 3 W TVE-Q up to height 2OO: maximum 2.5 W TVE-Q from height 3OO: maximum 3 W |
Power consumption (when running/when idle) | 1 W |
Setpoint value signal input (analogue optional) | 0 - 10 V DC, input resistance > 100 kΩ or 2 - 10V DC Ra> 50 kΩ |
Actual value signal output | O - 1O V DC or 2 - 1O V DC; maximum 5 mA |
lEC protection class | lll (Protective extra-low voltage) |
Protection level | lP 42 (with attached terminal cover) |
EC conformity | EMC to 2O14/3O/EU |
Bus connection | RS485, BACnet MS/TP or Modbus RTU |
Number of nodes (bus participants) | 128 |
BACnet communication parameters to be set | Baud rate adjustable: 96OO, 192OO, 384OO, 576OO, 768OO, 1152OO baud Start bit: 1 Data bits: 8 Stop bits: 1 no parity |
Adjustable communication parameters for Modbus | Baud rate adjustable: 12OO, 24OO, 48OO, 96OO, 192OO, 384OO, 768OO, 1152OO baud Start bit: 1 Data bits: 8 Stop bits adjustable: 1 or 2 Parity: adjustable: None, Even, Odd |
Setpoint / actual value interface | BACnet operation: via BACnet objects Modbus operation: via Modbus register list |
Bus termination | externally required (120 Ω) |
This specification text describes the general characteristics of the product.
Category
Application
Control of a constant or variable volume flow rate setpoint
Area of application
Dynamic transducer for clean air in ventilation and air conditioning systems
Actuator
Installation orientation
Connection
Terminals with cover by rubber cap, therefore no additional terminal box required
Supply voltage
Interface/signalling
BACnet MS/TP (RS485) or analogue signal 0 - 10 V DC or 2 - 10 V DC parameterised at the factory depending on the order option
Interface information
BACnet or Modbus: among other things, volume flow setpoint and actual value signal, damper position, override control
Special functions
Clearly visible external indicator light for signalling the functions: Set, not set, and power failure
Parameter setting
Specific parameters for VAV terminal unit are factory-set
Factory condition
Functional test under air using reference measurement on a regularly validated test bench in accordance with EN ISO 9001 to check the function and control accuracy of the complete volume flow controller
Equivalence criteria
TVE | – | D | / | P1 | / | 100 | / | D2 | / | XDMB0 | / | V | 0 | / | 20 - 350 [m³/h] |
| | | | | | | | | | | | | | | | | | |||||||
1 | 2 | 3 | 5 | 6 | 7 | 8 | 9 | 10 |
Type | TVE: VAV terminal unit |
Acoustic cladding | with acoustic cladding |
Material | Powder-coated RAL 7001 (silver grey) |
Nominal size [mm] | 100 |
Accessories | Double lip seal both ends |
Attachment (control component) | Volume flow controller with dynamic measuring principle, display and digital Bus interface for BACnet MS/TP, Modbus RTU and analogue interface |
Operating mode | variable operation, control with analogue signal |
Signal voltage range | 0 – 10 V DC |
Operating values for factory setting | 20 – 350 [m³/h] |
Sdílet stránku
Doporučit tuto stránku
Doporučit tuto stránku zasláním odkazu emailem.
Sdílet stránku
Děkujeme za doporučení!
Vaše doporučení bylo odesláno a zakrátko by mělo být doručeno.
Kontakt
Jsme tu pro vás
Uveďte prosím své sdělení a druh dotazu
Tel.: +420 283 880 380 | Fax: +420 286 881 870
Kontakt
Děkujeme vám za zprávu!
Vaše zpráva je odeslána a zakrátko bude zpracována.
Naše oddělení pro servisní dotazy se s vámi co nejrychleji spojí Pro obecné informace o výrobcích nebo o službách můžete také zavolat:
Tel.: +420 283 880 380 | Fax: +420 286 881 870
Kontakt
Jsme tu pro vás
Uveďte prosím své sdělení a druh dotazu
Tel.: +420 283 880 380 | Fax: +420 286 881 870
Kontakt
Děkujeme vám za zprávu!
Vaše zpráva je odeslána a zakrátko bude zpracována.
Naše oddělení pro servisní dotazy se s vámi co nejrychleji spojí Pro obecné informace o výrobcích nebo o službách můžete také zavolat:
Tel.: +420 283 880 380 | Fax: +420 286 881 870