BM0-J6

Control component with dynamic transducer with Modbus RTU interface and BACnet MS/TP interface for X-AIRCONTROL

Compact unit for VAV terminal unit TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVM

  • Controller, dynamic differential pressure transducer and actuator in one casing
  • Use in ventilation and air conditioning systems, only with clean air
  • Simple plug connection RJ12 for supply voltage and communication
  • Compatible with X-AIRCONTROL zone module Modbus
  • Volume flow rates qvmin and qvmax are pre-set in the factory and saved in the controller as changed parameters
  • High data transparency through standardised bus communication Modbus RTU or BACnet MS/TP
  • Setpoint value settings, override controls, parameter adjustment via bus communication or X-AIRCONTROL
  • Service access for manual adjustment devices and PC configuration software

 


General information

Application

  • All-in-one control engineering devices for VAV terminal units
  • Dynamic differential pressure transducer, electronic controller, and actuator are fitted together in one casing
  • Suitable for different control tasks depending on the specification of the setpoint value
  • The room temperature controller, central BMS, air quality controller or similar units control the variable volume flow control by specifying the setpoint values via a communication interface.
  • Suitable for room control X-AIRCONTROL zone module Modbus
  • Simple connection for supply voltage and communication with common RJ12 connection socket
  • Override controls for activating qvmin, qvmax, shut-off, OPEN position via Modbus register, BACnet objects or X-AIRCONTROL possible
  • Volume flow rate actual value is available as a network data point
  • Damper blade position is available as a network data point
  • Standard filtration in comfort air conditioning systems allows for use of the controller in the supply air without additional dust protection

 


With heavy dust levels in the room

  • Install appropriate exhaust air filters upstream, as a partial volume flow is routed through the transducer for volume flow rate measurement

 


If the air is contaminated with dust, fluff or sticky components

  • Use an attachment assembly with static differential pressure transducer



Control strategy

  • The volume flow controller works independently of the duct pressure
  • Differential pressure fluctuations do not result in permanent volume flow rate changes
  • To prevent the control from becoming unstable, a dead band is allowed within which the damper blade does not move
  • Flow rate range parameterised in the controller at the factory (qvmin: minimum volume flow rate, qvmax: maximum volume flow rate)
  • Operating parameters are specified via the order code and parameterised in the factory




Operating modes

  • Modbus RTU: Setpoint value setting via X-AIRCONTROL or external software
  • BACnet MS/TP: Setpoint value setting via external software




Interface

Communication interface

  • Modbus RTU, RS485 (factory preset)
  • BACnet MS/TP (can be activated on site with ZTH-EU)
  • Data points see bus lists

 





Parts and characteristics

  • Transducer for dynamic measurement principle
  • Overload protection
  • Connection socket RJ12
  • Service interface for connection of service tools
  • Axis clamping device
  • Indicator lights for detecting the operating mode
  • Addressing key for setting user addresses in bus mode
  • Supply and communication not galvanically isolated




Operating parameters

  • qvmin = 0 – 100 % of the nominal volume flow rate qvnom adjustable
  • qvmax = 20 – 100 % of the nominal volume flow rate qvnom adjustable




Construction


  • LMV-D3-M/B-J6 TR with connection socket RJ12
  • NMV-D3-M/B-J6 TR with connection socket RJ12

 

Type LMV-D3-M/B-J6 TR for volume flow controller

  • TVR, TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVM

 

Type NMV-D3-M/B-J6 TR for volume flow controller

  • TVJ
  • TVT up to 100 × 300 or 800 × 400 mm




Commissioning

  • Due to the volume flow rates set in the factory, always ensure that the control units are only installed in the specified locations

  • Commissioning steps for network integration required

  • Operating parameters can be adjusted by others (service tool ZTH-EU)





Useful additions

  • Adjustment device type ZTH (order code AT-VAV-B)


Technické údaje

Function, Specification text, Order code

  • Function
  • SPECIFICATION TEXT
  • ORDER CODE
      Principle of operation Funktionsgrafik_BM0ai.png

① Effective pressure transducer

② Actuator

③ Volume flow controller

④ Setpoint value signal

 

A closed control circuit for regulation of the volume flow rate, i.e. measuring - comparing - adjusting, is characteristic of air terminal units.
The volume flow rate is measured by measuring a differential pressure (effective pressure). This is done via a differential pressure sensor. An integrated differential pressure transducer converts the effective pressure into a voltage signal. The volume flow rate actual value is hence available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal volume flow rate (qvnom).
The volume flow rate setpoint value is specified by a higher-level controller (e.g. room temperature controller, air quality controller, central BMS). Variable volume flow control results in a value between qvmin and qvmax. It is possible to override the room temperature control, e.g. by a complete shut-off of the duct.
The controller compares the volume flow rate setpoint value to the actual value and controls the integral actuator accordingly.


Category

  • Compact controller for volume flow rate
  • Regulation of a constant or variable volume flow rate setpoint value
  • Electronic controller for connecting a controlled variable and tapping an actual value for integration in a Modbus RTU or BACnet MS/TP-based central building management system
  • The actual value relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified




Application

  • Dynamic transmitter for clean air in ventilation and air conditioning systems




Supply voltage

  • 24 V AC / DC




Actuator

  • Integrated; slow running (running time approx. 120 – 150 s for 90°)




Installation orientation

  • Either direction




Interface/signalling


  • Modbus RTU (RS-485)
  • BACnet MS/TP
  • Supply and communication not galvanically isolated
  • Termination switchable




Connection

  • Connection socket RJ12, suitable for TROX X-AIRCONTROL zone module X-AIR-ZMO-MOD




Interface information

  • Modbus Register
  • BACnet objects
  • Volume flow rate setpoint and actual value, damper blade position, error status, etc. read and write




Special functions


  • Activation Vmin, Vmax, closed, open via Modbus register or BACnet object

Optional activatable operating modes

  • Open loop: actuators with air flow measurement




Parameter setting

  • Parameters specific to VAV terminal unit parameterised at the factory
  • Operating values Vmin , Vmax  and interface type parameterised in the factory
  • Subsequent adjustment via Modbus-BACnet register access or via optional tools: adjustment device, PC software (wired in each case) possible




Factory condition

  • Electronic controller factory-mounted on the terminal unit
  • Factory parameter settings
  • Functional test under air; certified with sticker


TVRD / 100 / D2 / BM0-J6 / V / qvminqvmaxm³/h
||||||||
1256781011

1 Type
TVR VAV terminal unit

2 Acoustic cladding
No entry required: None
D With acoustic cladding 

3 Material
Galvanised sheet steel (Standard construction)
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction 

5 Nominal size [mm]
100, 125, 160, 200, 250 

6 Accessories

No entry required: None
D2 Double lip seal both sides
G2 Matching flanges both sides 

7 Attachments (control components)

BM0-J6 Compact controller of dynamic transducer, Modbus RTU, BACnet MS/TP, RJ12 connection socket

8 Operating mode
V Variable (setpoint value range) 

10 Operating values for factory setting
Volume flow rates in m³/h or l/
sqvconst (only with operating mode F)
qvmin (only with operating mode V, M)
qvmax (only with operating mode V, M) 

11 Volume flow rate unit
m³/h
l/s

Order example: TVT/200×100/D2/BM0-J6/V/200-800 m³/h
Acoustic claddingWithout
MaterialGalvanised sheet steel
Nominal size200 × 100 mm
AccessoriesDouble lip seal both sides
AttachmentCompact controller Modbus, dynamic transducer, Modbus RTU, BACnet MS/TP, RJ12 connection socket
Operating modeV variable operation
Volume flow rate200 – 800 m³/h

 

Variants

  • VARIANTS


Technical data, Product details

  • TECHNICAL DATA, PRODUCT DETAILS

Compact controllers for VAV terminal units

VAV terminal units

Type of installation componentPart number
TVR, TZ-Silenzio, TA-Silenzio, TVZ, TVA

LMV-D3-M/B-J6 TR

A00000070622

TVJ, TVT

NMV-D3-M/B-J6 TR

A00000070621

TVM

2 x LMV-D3-M/B-J6 TR

A00000070622


 

 




Compact controller BM0-J6, LMV-D3-M/B-J6 TR


Supply voltage (AC)

24 V AC, 50/60 Hz

Supply voltage (DC)

24 V DC

Power rating (AC)

Max. 4 VA (max. 8 A @ 5 ms)

Power rating (DC)

Max. 2 W

Functional range

AC 19.2 – 28.8 V/DC 21.6 – 28.8 V

Bus connection

Modbus RTU**, BACnet MS/TP,



Adjustable communication parameters Modbus RTU


Baud rate: 9600, 19200, 38400**, 76800, 115200;



Address: 1**,2.3 – 247;



Parity: 1-8-N-2**, 1-8-N-1, 1-8-E-1, 1-8-O-1;



Number of nodes: max. 32 (without repeater)



Terminal resistor: 120 Ω;



Adjustable communication parameters BACnet MS/TP




Baud rate: 9600, 19200, 38400**,76800, 115200;

Address: 0,1**,2.3 – 127;

Number of nodes: max. 32 (without repeater)

Terminal resistor: 120 Ω;


Addressing

Required on-site: e.g. adjustment device ZTH-EU or external software

Setpoint value signal input

Via Modbus register access e.g. via X-AIRCONTROL zone module or BACnet objects

IEC protection class

III (protective extra-low voltage)

EC conformity

EMC to 2014/30/EU


**Factory setting





Compact controller BM0-J6, NMV-D3-M/B-J6 TR


Supply voltage (AC)

24 V AC, 50/60 Hz

Supply voltage (DC)

24 V DC

Power rating (AC)

Max. 5 VA (max. 8 A @ 5 ms)

Power rating (DC)

Max. 3 W

Functional range

AC 19.2 – 28.8 V/DC 21.6 – 28.8 V

Bus connection

Modbus RTU**, BACnet MS/TP,



Adjustable communication parameters Modbus RTU




Baud rate: 9600, 19200, 38400**, 76800, 115200;

Address: 1**,2.3 – 247;

Parity: 1-8-N-2**, 1-8-N-1, 1-8-E-1, 1-8-O-1;

Number of nodes: max. 32 (without repeater)

Terminal resistor: 120 Ω;


Adjustable communication parameters BACnet MS/TP

Baud rate: 9600, 19200, 38400**, 76800, 115200;



Address: 0,1**,2.3 – 127;



Number of nodes: max. 32 (without repeater)



Terminal resistor: 120 Ω;

Addressing

Required on-site: e.g. adjustment device ZTH-EU or external software

Setpoint value signal input

Via Modbus register access e.g. via X-AIRCONTROL zone module or BACnet objects

IEC protection class

III (protective extra-low voltage)

EC conformity

EMC to 2014/30/EU


**Factory setting



 

 

 

 

 

 

 

 


Communication interface Modbus RTU


NumberRegister AddressDescriptionRange EnumerationUnitScalingAccess
1

Setpoint value

Setpoint value between qvmin and qvmax

0 – 10000

Factory setting: 0

%

0.01[R / W]
21

Override control

Overwrites the setpoint value with override control

0: None

1: OPEN

2: CLOSED

3: qvmin

4: qvmid

5: qvmax

Factory setting: None (0)

-

-[R / W]
32

Command triggering -

Release of functions for service and test purposes. Reset resets the controller and clears internal error memory such as register 105.

 

0: None

1: Adaptation

2: Test

3: Synchronisation

4: Reset

Factory setting: None (0)

-

-[R / W]
43

Type of actuator

0: Actuator not connected/not known


1: Actuator air/water with/without safety function


2: Volume flow controller VAV/EPIV


3: Fire damper


4: Energy valve


5: Pressure-independent control valve

-

-[R]
54

Current damper blade position (%)

0 – 10000

%

0.01[R]
65

Damper blade angle (°)

0 – max.

°

1[R]
76

Relative volume flow rate related to qvnom;

0 – 10000

%

0.01[R]
87

Absolute volume flow rate related to qvnom;

0 – qvnom;

m³/h

 

1[R]
109

-

-

-

-[–]
1110

Absolute volume flow rate in selected volume flow unit acc. to register 15 (Lowword)

-

UnitSel

0.0001[R]
1211

Absolute volume flow rate in selected volume flow unit acc. to register 15 (Highword)

-

UnitSel

0.0001[R]
1312

Analogue setpoint value (%).

Shows the setpoint value in % with control input signal.

0 – 10000

%

0.01[R]
10099

Bus terminal resistor.

Indicates whether the terminating resistor (120 Ω) is active or deactivated.

0: inactive

1: active

Factory setting: inactive (0)

-

-[R / W]
101100

Serial number, part 1

-

-

-[R]
102101

Serial number, part 2

-

-

-[R]
103102

Serial number, part 3

-

-

-[R]
104103

Firmware version.

Example: 302, version 3.02

-

-

-[R]
105104

Malfunctions and service information

Bit1: Mechanical travel exceeded

Bit2: Actuator cannot be moved (e.g. mechanical overload)

Bit8: Internal activity (e.g. test run, adaptation)

Bit9: Gear release active

Bit10: Bus monitoring triggered

-

-[R]
106105

Setting work areas qvmin

Requirements qvminvmax

qvmin in the area 0 – 100 % qvnom;

0 – qvmax

Standard: 0

%

0.001[R / W]
107106

Setting work areas qvmax

Requirements qvmaxvmin

Vmax in the area 20 - 100 % qvnom;

qvmin 10000

Standard: 10000

%

0.01[R / W]
109108

Bus timeout monitoring

0: Last setpoint value

1: Fast close — CLOSED

2: Quick open — OPEN

3: Center position

Factory setting: Last setpoint value (0)

-

-[R / W]
110109

Time until release bus timeout monitoring

0 - 3600 seconds

Factory setting: 0 (bus timeout monitoring deactivated)

 

s

1[R / W]
111110

Nominal volume flow rate qvnom; (m³/h)

-

m³/h

1[R]
112111

-

-

-

-[–]
113112

Nominal volume flow rate qvnom; in selected volume flow unit acc. to Reg 118 (LowWord)

-

UnitSel

0.001[R]
114113

Nominal volume flow rate qvnom; in selected volume flow unit acc. to 118 (HighWord)

-

UnitSel

0.001[R]
115114

-

-

-

-[–]
116115

-

-

-

-[–]
117116

Control mode

0: Position control (open loop)

1: Volume flow control

-

-[R / W]
118117

Unit selection

0: m³/s

1: m³/h

2: l/s

3: l/min

4: l/h

5: gpm

6: cfm

Standard m³/h (1)

-

-[R / W]
119118

Setpoint value setting

 

0: Analogue (0 – 10 V, 2 – 10 V)

1: Bus (Modbus, BACnet,)

Factory setting: Bus (1)

-

-[R / W]

 

 




 




Communication interface BACnet MS/TP


Object NameObject TypeDescriptionValuesCOV IncrementAccess
DeviceDevice [Inst.No]

0 – 4194302
Default: 1

-

W
RelPosAI[1]

Damper blade position in %

Overridden = 1 (gear latch pressed)

0 – 100

0.01 – 100

Standard: 1

AbsPosAI[2]

Absolute position in °

Overridden = 1 (gear latch pressed)

 

0 - max. rotation angle

0.01 – 65353

Factory setting: 1

SpAnalogueAI[6]

Analogue setpoint value in %


 


Shows the analogue setpoint value in %, if setpoint value setting is in (SpSource[122]) Analogue (1)


If setpoint value setting (SpSource[122]) Bus (2) = then Out_Of_Service is TRUE


 

0 – 100

0.01 – 100

Standard: 1

RelFlowAI[10]

Relative volume flow rate in %

0 – 100

0.01 – 100

Standard: 1

AbsFlow_UnitSelAI[19]

Absolute volume flow rate of selected unit acc. to [121]

 

0 – qvnom;

0.01 – 1000

Standard: 1

SpRelAO[1]

Relative setpoint value in %

 

Setpoint value between qvmin AV[97] and qvmax [98] (Only with bus control input signal)

If SpSource (MV[122]) = 1 (Analogue), then Out_of_Service = TRUE   

0 – 100

Factory setting: 0

0.01 – 100

Factory setting: 1

C
Min.AV[97]

Minimum setpoint value in % (qvmin)

Requirement:

qvminvmax

qvmin in the area 0 - 100 & qvnom;

0 – qvmax 

Factory setting: 0

0.01 – 100

Factory setting: 1

W
Max.AV[98]

Minimum setpoint value in % (qvmax)

Requirement:

qvmax > qvmin

qvmax in the area 20 - 100 % of qvnom;

qvmin  – 100

Standard: 100

0.01 – 100

Standard: 1

W
Vnom_UnitSelAV[104]

Current volume flow rate according to selected volume flow unit (UnitSelFlow MV[121])

 

-

0.01 – 100

Standard: 1

Bus WatchdogAV[130]

Time until the release bus timeout monitoring in s


If Present_Value ≠ 0, then write access to Present_Value is monitored by AO[1] and MO[1]. Writing to Present_Value AO[1] MO[1] resets the timer.
In hybrid mode, only write accesses to MO[1] are monitored.

0 – 3600 s

Factory setting: 0 (bus timeout monitoring deactivated)

0.01 – 1000

Standard: 1

W
BusTerminationBI[99]

Terminal resistor

 

Shows whether the terminal resistor (120 Ω) has been activated via the service tools.

 

Inactive_Text: Switch not active

Active_Text: Switch active

-

SummaryStatusBI[101]

Condensed status

Summary status (MI[106], MI[110])

Inactive_Text: no error

Active_Text: Error

-

InternalActivity

MI[100]

Status Activity

 

1: None

2: Test

3: Adaptation

-

StatusActuator

MI[106]

Status of the actuator

1: OK

2: Actuator cannot be moved

3: Gear release active

4: Mechanical travel exceeded

-

StatusDevice

MO[110]

Status of the device

Shows the general status of the device

1: OK

2: Bus timeout monitoring activated

-

Override

MO[1]

Override control

Overwrites the setpoint value (SpRel AO[1]) with a forced command.

1: None

2: OPEN

3: CLOSED

4: qvmin

5: qvmid

6: qvmax

Factory setting: None (1)

-

C
Command

MV[120]

Release test functions

1: None

2: Adaptation

3: Test

4: Reset

Factory setting: None (1)

-

W
UnitSelFlow

MV[121]

Unit selection

The selected unit is indicated in AI[19] and AV[104].

1: m³/s

2: m³/h

3: l/s

4: l/min

5: l/h

6: gpm

7: cfm

Factory setting: m³/h (2)

-

W
ControlMode

MV[122]

Setpoint value setting

1: Analogue (0 – 10 V, 2 – 10 V)

2: Bus (Modbus, BACnet, MP-Bus)

Factory setting: Bus (2)

-

W
ControlMode

MV[223]

ControlMode

 

1: Position control (OpenLoop)

2: Volume flow control

-

W

Stažení

informace o produktu

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"1; mode=block", "x-content-type-options"=>"nosniff", "x-download-options"=>"noopen", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8"}

Sdílet stránku

Doporučit tuto stránku

Doporučit tuto stránku zasláním odkazu emailem.

Pole označená (*) jsou povinná.

Sdílet stránku

Děkujeme za doporučení!

Vaše doporučení bylo odesláno a zakrátko by mělo být doručeno.


Kontakt

Jsme tu pro vás

Uveďte prosím své sdělení a druh dotazu
Tel.: +420 283 880 380 | Fax: +420 286 881 870

Pole označená (*) jsou povinná.

Kontakt

Děkujeme vám za zprávu!

Vaše zpráva je odeslána a zakrátko bude zpracována.
Naše oddělení pro servisní dotazy se s vámi co nejrychleji spojí Pro obecné informace o výrobcích nebo o službách můžete také zavolat:
Tel.: +420 283 880 380 | Fax: +420 286 881 870

Kontakt

Jsme tu pro vás

Uveďte prosím své sdělení a druh dotazu
Tel.: +420 283 880 380 | Fax: +420 286 881 870

Attachment (max. 10MB)

Pole označená (*) jsou povinná.

Kontakt

Děkujeme vám za zprávu!

Vaše zpráva je odeslána a zakrátko bude zpracována.
Naše oddělení pro servisní dotazy se s vámi co nejrychleji spojí Pro obecné informace o výrobcích nebo o službách můžete také zavolat:
Tel.: +420 283 880 380 | Fax: +420 286 881 870