Jet nozzles are the preferred solution wherever the supply air has to travel large distances from the point of discharge to the occupied zone. It is possible to adapt the discharge angle, and consequently the direction of the airflow, to heating or cooling mode. The supply air to room air temperature difference can be -12 - +20 K.
Cooling mode
Cooling mode is possible with a positive discharge angle of up to 30°. The supply air jet is directed towards the ceiling, but the higher density of cold air results in an increasing deflection of the air jet towards the floor as the distance from the jet nozzle increases. When the supply air jet reaches the occupied zone, both the supply air to room air temperature difference and the airflow velocity have been reduced to comfortable levels. This principle of operation allows for long throw distances.
Heating mode
Heating operation is possible with a negative discharge angle of -30° or less. The supply air jet is directed towards the occupied zone. Due to the lower density of warm air, the jet becomes buoyant. When the supply air jet reaches the occupied zone, both the supply air to room air temperature difference and the airflow velocity should ideally have been reduced.
The discharge angle can be changed manually or with a thermal or electric actuator.
A swirl unit and cap (optional) allow for reducing the throw distance to 65 % or 75 %.
Nominal sizes | 160, 200, 250, 315, 400 mm |
Volume flow rate range | 20 – 1000 l/s or 72 – 3600 m³/h |
Adjustable discharge angle | -30 – +30° |
Supply air to room air temperature difference | -12 to +20 K |
Quick sizing tables provide a good overview of the volume flow rates and corresponding sound power levels and differential pressures.
Exact values for all parameters can be determined with our Easy Product Finder design program.
Sound power level and total differential pressure
NS | qv [l/s] | qv (m³/h) | Δpt [Pa] | LWA [dB(A)] | vL | |
---|---|---|---|---|---|---|
0.5 m/s | 1.0 m/s | |||||
L [m] | L | |||||
160 | 20 | 72 | 9 | < 15 | < 5 | < 5 |
40 | 144 | 34 | < 15 | 8 | < 5 | |
60 | 216 | 76 | 15 | 13 | 6 | |
80 | 288 | 135 | 26 | 17 | 8 | |
200 | 35 | 126 | 9 | < 15 | 6 | < 5 |
70 | 252 | 35 | < 15 | 11 | 6 | |
105 | 378 | 78 | 19 | 17 | 9 | |
140 | 504 | 138 | 30 | 23 | 11 | |
250 | 55 | 198 | 8 | < 15 | 7 | < 5 |
110 | 396 | 33 | < 15 | 14 | 7 | |
165 | 594 | 75 | 21 | 21 | 11 | |
220 | 792 | 132 | 33 | 28 | 14 | |
315 | 90 | 324 | 8 | < 15 | 9 | < 5 |
185 | 666 | 35 | < 15 | 18 | 9 | |
265 | 954 | 71 | 24 | 26 | 13 | |
360 | 1296 | 132 | 36 | > 30 | 18 | |
400 | 155 | 558 | 8 | < 15 | 12 | 6 |
310 | 1116 | 33 | < 15 | 24 | 12 | |
465 | 1674 | 75 | 27 | > 30 | 18 | |
620 | 2232 | 133 | 38 | > 30 | 24 |
All values apply to discharge angle 0°
L: Throw distance with isothermal operation, no throw distance reduction
Adjustable jet nozzles for the ventilation of large internal spaces such as halls and assembly rooms. Air discharge with long throw distance, excellent acoustic properties. Nozzles tilt vertically from –30 - +30° for horizontal air discharge. Discharge angle indication, discharge angle limiting and setting on a concealed scale.
Consists of a casing for the spherical discharge nozzle, flange, face cover ring and nozzle.
For push fitting directly onto circular ducts or as a branch off circular or rectangular ducts.
Special features
Maintenance
Materials and surfaces
TJN | – | R | – | E7 | / | 160 | – | 315 | / | C | / | D | / | S1 |
| | | | | | | | | | | | | | | | |||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | |||||||
Type | TJN |
Connection piece | For rectangular ducts |
Actuator | Modulating, 2 – 10 V DC, 24 V AC |
Nominal size | 250 mm |
Attachments | Outer casing |
Accessories | Swirl unit and cap for throw distance reduction |
Exposed surface | White aluminium, similar to RAL 9006 |
General information
Together with renowned designers and architects we have developed ceiling, wall, staircase and floor diffusers and grilles that are not only aesthetic design elements, but also meet demanding ventilation and acoustic requirements.
NS | TJN | TJN-E* | TJN-T1 | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD4 | ØD | C | |
160 | 192 | 1.9 | 192 | 2.1 | 252 | 2.3 | 258 | 15 | 227 | 158 | 50 |
200 | 200 | 2.3 | 200 | 2.5 | 260 | 2.8 | 298 | 14 | 263 | 198 | 50 |
250 | 210 | 3.1 | 210 | 3.3 | 270 | 3.7 | 348 | 14 | 315 | 248 | 50 |
315 | 225 | 4.0 | 225 | 4.2 | 285 | 4.8 | 413 | 15 | 379 | 313 | 50 |
400 | 235 | 4.6 | 235 | 4.8 | 295 | 5.5 | 501 | 16 | 468 | 398 | 50 |
TJN/.../C
NS | TJN/.../C | TJN-E*/.../C | TJN-T1/.../C | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD3 | ØD | C | |
160 | 192 | 2.7 | 192 | 2.9 | 252 | 3.4 | 258 | 15 | 228 | 158 | 50 |
200 | 200 | 3.4 | 200 | 3.6 | 260 | 4.2 | 298 | 14 | 265 | 198 | 50 |
250 | 210 | 4.4 | 210 | 4.6 | 270 | 5.3 | 348 | 14 | 316 | 248 | 50 |
315 | 225 | 5.8 | 225 | 6.0 | 285 | 7.0 | 413 | 15 | 381 | 313 | 50 |
400 | 235 | 8.0 | 235 | 8.2 | 295 | 9.5 | 501 | 16 | 469 | 398 | 50 |
NS | TJN-K | TJN-K-T1 | TJN-E*/.../C | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD4 | ØD | C | |
160 | 248 | 2.1 | 308 | 2.5 | 248 | 2.3 | 258 | 15 | 227 | 158 | 50 |
200 | 257 | 3.2 | 317 | 3.7 | 257 | 3.4 | 298 | 14 | 263 | 198 | 50 |
250 | 265 | 3.4 | 325 | 4.0 | 265 | 3.6 | 348 | 14 | 315 | 248 | 50 |
315 | 281 | 4.6 | 341 | 5.4 | 281 | 4.8 | 413 | 15 | 379 | 313 | 50 |
400 | 292 | 6.5 | 352 | 7.4 | 292 | 6.7 | 501 | 16 | 468 | 398 | 50 |
NS | TJN-K/.../C | TJN-K-E*/.../C | TJN-K-T1/.../C | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD3 | ØD | C | |
160 | 258 | 3.5 | 258 | 3.7 | 318 | 4.2 | 258 | 15 | 228 | 158 | 50 |
200 | 267 | 4.3 | 267 | 4.5 | 327 | 5.1 | 298 | 14 | 265 | 198 | 50 |
250 | 276 | 5.5 | 276 | 5.7 | 336 | 6.4 | 348 | 14 | 316 | 248 | 50 |
315 | 291 | 7.2 | 291 | 7.4 | 351 | 8.4 | 413 | 15 | 381 | 313 | 50 |
400 | 302 | 9.9 | 302 | 10.1 | 362 | 11.4 | 501 | 16 | 469 | 398 | 50 |
NS | TJN-R | TJN-R-E* | TJN-R-T1 | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD4 | ØD | C | |
160 | 248 | 2.1 | 248 | 2.3 | 308 | 2.5 | 258 | 15 | 227 | 158 | 50 |
200 | 257 | 3.2 | 257 | 3.4 | 317 | 3.7 | 298 | 14 | 263 | 198 | 50 |
250 | 265 | 3.4 | 265 | 3.6 | 325 | 4.0 | 348 | 14 | 315 | 248 | 50 |
315 | 281 | 4.6 | 281 | 4.8 | 341 | 5.4 | 413 | 15 | 379 | 313 | 50 |
400 | 292 | 6.5 | 292 | 6.7 | 352 | 7.4 | 501 | 16 | 468 | 398 | 50 |
NS | TJN-R/.../C | TJN-R-E*/.../C | TJN-R-T1/.../C | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
L2 | m [kg] | L2 | m [kg] | L2 | m [kg] | ØD1 | L1 | ØD3 | ØD | C | |
160 | 261 | 3.5 | 261 | 3.7 | 321 | 4.2 | 258 | 15 | 228 | 158 | 50 |
200 | 270 | 4.3 | 270 | 4.5 | 330 | 5.1 | 298 | 14 | 265 | 198 | 50 |
250 | 279 | 5.5 | 279 | 5.7 | 339 | 6.4 | 348 | 14 | 316 | 248 | 50 |
315 | 294 | 7.2 | 294 | 7.4 | 354 | 8.4 | 413 | 15 | 381 | 313 | 50 |
400 | 305 | 9.9 | 305 | 10.1 | 365 | 11.4 | 501 | 16 | 469 | 398 | 50 |
NS | 315 | 500 | 630 | 800 |
---|---|---|---|---|
160 | + | + | + | + |
200 | + | + | + | |
250 | + | + | + | |
315 | + | + | + | |
400 | + | + |
Installation and commissioning
The illustrations are schematic and serve to create a better understanding of the installation details.
TJN
NS | ØD1 | ØD2 | Aeff [m2] |
---|---|---|---|
160 | 258 | 82 | 0.00500 |
200 | 298 | 108 | 0.00850 |
250 | 348 | 136 | 0.0135 |
315 | 413 | 174 | 0.0225 |
400 | 501 | 231 | 0.0385 |
Sdílet stránku
Doporučit tuto stránku
Doporučit tuto stránku zasláním odkazu emailem.
Sdílet stránku
Děkujeme za doporučení!
Vaše doporučení bylo odesláno a zakrátko by mělo být doručeno.
Kontakt
Jsme tu pro vás
Uveďte prosím své sdělení a druh dotazu
Tel.: +420 283 880 380 | Fax: +420 286 881 870
Kontakt
Děkujeme vám za zprávu!
Vaše zpráva je odeslána a zakrátko bude zpracována.
Naše oddělení pro servisní dotazy se s vámi co nejrychleji spojí Pro obecné informace o výrobcích nebo o službách můžete také zavolat:
Tel.: +420 283 880 380 | Fax: +420 286 881 870
Kontakt
Jsme tu pro vás
Uveďte prosím své sdělení a druh dotazu
Tel.: +420 283 880 380 | Fax: +420 286 881 870
Kontakt
Děkujeme vám za zprávu!
Vaše zpráva je odeslána a zakrátko bude zpracována.
Naše oddělení pro servisní dotazy se s vámi co nejrychleji spojí Pro obecné informace o výrobcích nebo o službách můžete také zavolat:
Tel.: +420 283 880 380 | Fax: +420 286 881 870