Application
Safety function
Parts and characteristics
Functional description
The actuator moves the blades of a multileaf damper into OPEN or CLOSED position.
Control input signal with 1-wire control (2-point).
1-wire control is actually an open/close control.
Any attachments are to be defined with the order code of the multileaf damper.
Spring return actuators for multileaf dampers
ZF01 | M466ET0 | NF24A | – | 10 Nm | 24 V |
ZF02 | M466ET1 | NFA | – | 10 Nm | 24 – 240 V AC 24 – 125 V DC |
ZF03 | M466ET2 | NF24A-S2 | integrated | 10 Nm | 24 V |
ZF04 | M466ET3 | NFA-S2 | integrated | 10 Nm | 24 – 240 V AC 24 – 125 V DC |
ZF06 | M466ER9 | SF24A | – | 20 Nm | 24 V |
ZF07 | M466ER8 | SFA | – | 20 Nm | 24 – 240 V AC 24 – 125 V DC |
ZF08 | M466ER6 | SF24A-S2 | integrated | 20 Nm | 24 V |
ZF09 | M466ER7 | SFA-S2 | integrated | 20 Nm | 24 – 240 V AC 24 – 125 V DC |
ZF11 | M466ET5 | EF24A | – | 30 Nm | 24 V |
ZF12 | M466ET6 | EF230A | – | 30 Nm | 100 – 240 V AC |
ZF13 | M466ET7 | EF24A-S2 | integrated | 30 Nm | 24 V |
ZF14 | M466ET8 | EF230A-S2 | integrated | 30 Nm | 100 – 240 V AC |
Application
Variants
Safety function
Parts and characteristics
Spring return actuator NF24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC –10 %, +20 % |
Power consumption – load | 6 W |
Power consumption – idle | 2.5 W |
Power rating | 8.5 VA |
Torque | 10 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Connecting cable | 2 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 1.8 kg |
Spring return actuator NF24A-S2
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC –10 %, +20 % |
Power consumption – load | 6 W |
Power consumption – idle | 2.5 W |
Power rating | 8.5 VA |
Torque | 10 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Auxiliary switch: type of contact | 2 changeover contacts1) |
Max. switching voltage (AC) | 250 V AC |
Max. switching current (AC) | 3 A (resistive load); 0.5 A (inductive load) |
Max. switching voltage (DC) | 110 V DC |
Max. switching current (DC) | 0.5 A (resistive load); 0.2 A (inductive load) |
Connecting cable – actuator | 2 × 0.75 mm², 1 m long |
Connecting cable – auxiliary switch | 6 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 2.0 kg |
1) If both auxiliary switches are used the switching voltages must be the same
Spring return actuator SF24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC –10 %, +20 % |
Power rating (AC) | 7.5 VA max. |
Power rating (DC) | 5 W max. |
Torque | 20 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Connecting cable | 2 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 2.1 kg |
Spring return actuator SF24A-S2
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ±10 % |
Power rating (AC) | 7.5 VA max. |
Power rating (DC) | 5 W max. |
Torque | 20 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Auxiliary switch: type of contact | 2 changeover contacts1) |
Max. switching voltage (AC) | 250 V AC |
Max. switching current (AC) | 3 A (resistive load); 0.5 A (inductive load) |
Max. switching voltage (DC) | 110 V DC |
Max. switching current (DC) | 0.5 A (resistive load); 0.2 A (inductive load) |
Connecting cable – actuator | 2 × 0.75 mm², 1 m long |
Connecting cable – auxiliary switch | 6 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 2.3 kg |
1) If both auxiliary switches are used the switching voltages must be the same
Spring return actuator EF24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ±10 % |
Power rating (AC) | 16 VA max. |
Power rating (DC) | 9.5 W max. |
Torque | 30 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Connecting cable | 2 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 4.3 kg |
Spring return actuator EF24A-S2
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ±10 % |
Power rating (AC) | 16 VA max. |
Power rating (DC) | 9.5 W max. |
Torque | 30 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Auxiliary switch: type of contact | 2 changeover contacts¹⁾ |
Max. switching voltage (AC) | 250 V AC |
Max. switching current (AC) | 3 A (resistive load); 0.5 A (inductive load) |
Max. switching voltage (DC) | 110 V DC |
Max. switching current (DC) | 0.5 A (resistive load); 0.2 A (inductive load) |
Connecting cable – actuator | 2 × 0.75 mm², 1 m long |
Connecting cable – auxiliary switch | 6 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 4.4 kg |
¹⁾ If both auxiliary switches are used the switching voltages must be the same
Application
Variants
Safety function
Parts and characteristics
Spring return actuator EF230A
Supply voltage (AC) | 100 – 240 V AC ±10 %, 50/60 Hz |
Power rating (AC) | 21 VA max. |
Torque | 30 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Connecting cable | 2 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 4.2 kg |
Spring return actuator EF230A-S2
Supply voltage (AC) | 100 – 240 V AC ±10 %, 50/60 Hz |
Power rating (AC) | 21 VA max. |
Torque | 30 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Auxiliary switch: type of contact | 2 changeover contacts¹⁾ |
Max. switching voltage (AC) | 250 V AC |
Max. switching current (AC) | 3 A (resistive load); 0.5 A (inductive load) |
Max. switching voltage (DC) | 110 V DC |
Max. switching current (DC) | 0.5 A (resistive load); 0.2 A (inductive load) |
Connecting cable – actuator | 2 × 0.75 mm², 1 m long |
Connecting cable – auxiliary switch | 6 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 4.6 kg |
¹⁾ If both auxiliary switches are used the switching voltages must be the same
Application
Variants
Safety function
Parts and characteristics
Spring return actuator NFA
Supply voltage (AC) | 24 – 240 V AC –20 % +10 %, 50/60 Hz |
Supply voltage (DC) | 24 – 125 V DC ±10 % |
Power consumption – load | 6 W |
Power consumption – idle | 2.5 W |
Power rating | 9.5 VA |
Torque | 10 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Connecting cable | 2 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 2.0 kg |
Spring return actuator NFA-S2
Supply voltage (AC) | 24 – 240 V AC –20 % +10 %, 50/60 Hz |
Supply voltage (DC) | 24 – 125 V DC ±10 % |
Power consumption – load | 6 W |
Power consumption – idle | 2.5 W |
Power rating | 9.5 VA |
Torque | 10 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Auxiliary switch: type of contact | 2 changeover contacts1) |
Max. switching voltage (AC) | 250 V AC |
Max. switching current (AC) | 3 A (resistive load); 0.5 A (inductive load) |
Max. switching voltage (DC) | 110 V DC |
Max. switching current (DC) | 0.5 A (resistive load); 0.2 A (inductive load) |
Connecting cable – actuator | 2 × 0.75 mm², 1 m long |
Connecting cable – auxiliary switch | 6 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 2.2 kg |
1) If both auxiliary switches are used the switching voltages must be the same
Spring return actuator SFA
Supply voltage (AC) | 19.2 – 264 V AC, 50/60 Hz |
Supply voltage (DC) | 21.6 – 137 V DC |
Power rating (AC) | 18 VA max. |
Power rating (DC) | 7 W max. |
Torque | 20 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Connecting cable | 2 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 2.2 kg |
Spring return actuator SFA-S2
Supply voltage (AC) | 19.2 – 264 V AC, 50/60 Hz |
Supply voltage (DC) | 21.6 – 137 V DC |
Power rating (AC) | 18 VA max. |
Power rating (DC) | 7 W max. |
Torque | 20 Nm |
Motor running time for 90° | < 75 s |
Spring return time | 20 s (for < −20 °C up to 60 s) |
Control input signal | Supply voltage on/off |
Auxiliary switch: type of contact | 2 changeover contacts1) |
Max. switching voltage (AC) | 250 V AC |
Max. switching current (AC) | 3 A (resistive load); 0.5 A (inductive load) |
Max. switching voltage (DC) | 110 V DC |
Max. switching current (DC) | 0.5 A (resistive load); 0.2 A (inductive load) |
Connecting cable – actuator | 2 × 0.75 mm², 1 m long |
Connecting cable – auxiliary switch | 6 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 2.4 kg |
1) If both auxiliary switches are used the switching voltages must be the same
Sdílet stránku
Doporučit tuto stránku
Doporučit tuto stránku zasláním odkazu emailem.
Sdílet stránku
Děkujeme za doporučení!
Vaše doporučení bylo odesláno a zakrátko by mělo být doručeno.
Kontakt
Jsme tu pro vás
Uveďte prosím své sdělení a druh dotazu
Tel.: +420 283 880 380 | Fax: +420 286 881 870
Kontakt
Děkujeme vám za zprávu!
Vaše zpráva je odeslána a zakrátko bude zpracována.
Naše oddělení pro servisní dotazy se s vámi co nejrychleji spojí Pro obecné informace o výrobcích nebo o službách můžete také zavolat:
Tel.: +420 283 880 380 | Fax: +420 286 881 870
Kontakt
Jsme tu pro vás
Uveďte prosím své sdělení a druh dotazu
Tel.: +420 283 880 380 | Fax: +420 286 881 870
Kontakt
Děkujeme vám za zprávu!
Vaše zpráva je odeslána a zakrátko bude zpracována.
Naše oddělení pro servisní dotazy se s vámi co nejrychleji spojí Pro obecné informace o výrobcích nebo o službách můžete také zavolat:
Tel.: +420 283 880 380 | Fax: +420 286 881 870